Installation manual
Installation Manual
150933 / Rev. 9/96 17
4.7 DIP Switch Settings
A 5-position DIP switch on the 5395 board allows you to select the following:
•
How long the 5395 will wait before indicating a loss of AC.
•
Which input (Input 1 or Input 2) will control the notification outputs.
•
Which outputs to wire as class A and class B.
•
Auxiliary power state.
•
Which outputs to operate as steady outputs or ANSI temporal.
Refer to Figure 4-2 on page 11 for the location of the DIP switch on the 5395 board.
4.7.1  Selecting the Input/Output Configuration
Figure 4-7 shows the position of each switch on the DIP switch for various input and output
configurations. The position of switch 4 and 5 do not affect the relationship of inputs to outputs.
Note: The 5395 checks switches 1, 2, and 3 only when powering up the 5395. If you change
these switch settings, you must remove both the AC power and the battery to force the
5395 to recognize the new switch settings.
12
3
45
12
3
45
Switch 1-3
OFF
*Switch1-2OFF
Switch3ON
Switch 1, 3 OFF
Switch2ON
12
3
4
5
Switch 1 OFF
Switch 2-3 ON
12
3
4
5
* See the followin
g
information about ANSI temporal-coded outputs