Installation manual
Model 5395 Distributed Power Module
14 150933 / Rev. 9/96
Class B Supervised Input Circuits
Figure 4-5 shows class B supervised wiring from a fire panel to the Model 5395 board.
Use an EOL resistor as shown to enable notification input supervision. Some panels use EOLs
that have a different value than the 4.7k ohm EOL resistor used by the 5395. In this case, the
EOL must be UL listed for the fire panel (not the 5395).
9
1
Input 2
10
211
3
12
4
13
5
14
6
15
716
8
17 18 19
Model
5395
Input 1
Trouble
Relay
-
+
Class B notification
output from fire panel
classbin
EOL
(must be UL listed
for the fire panel)
Supervised
Notification
Circuits
-
+
Class B
Model 7628
4.7k EOL
Model 7628
4.7k EOL
OUT1OUT2
OUT3
OUT4
AUX
Figure 4-5. Class B Supervised Input/Output Connections