Specifications

Model SK-6324 Fire Control Panel Installation/Operation Manual
5-2 151117
Zone 2 1
Enhanced Mode On 5 On
Enhanced mode. Use when both pull
stations and detectors will be used in the
same zone.
Enhanced Mode Off 5 Off
Normal mode. Use when 2- or 4-wire
smoke detectors and smoke verification
are used in the same zone.
Alarm Verification On 6 On
Alarm Verification
Note:
Do not use with smoke
detectors that have verification built-
in.
Alarm Verification Off 6 Off No verification
Zone Types
Fire Zone
7 Off
8 Off
Supervisory Zone
7 On
8 Off
Water Flow Zone No
Delay
7 Off
8 On
Water Flow Zone
With Delay
7 On Refer to “General Options” to program
the Water Flow delay time.
8 On
Zone 3 2
Enhanced Mode On 1 On
Enhanced mode. Use when both pull
stations and detectors will be used in the
same zone.
Enhanced Mode Off 1 Off
Normal mode. Use when 2- or 4-wire
smoke detectors and smoke verification
are used in the same zone.
Alarm Verification On 2 On
Alarm Verification
Note:
Do not use with smoke
detectors that have verification built-
in.
Alarm Verification Off 2 Off No verification
Zone Types
Fire Zone
3 Off
4 Off
Supervisory Zone
3 On
4 Off
Water Flow Zone No
Delay
3 Off
4 On
Water Flow Zone
With Delay
3 On Refer to “General Options” to program
the Water Flow delay time.
4 On
Table 5-1: DIP Switch Programming
Options
Dip Switch
Number
Feature
Switch
Number
Comments