Specifications
151117 5-1
Section 5
S
y
stem Confi
g
uration
To configure the SK-6324 system set the dipswitch that controls the option you want to
select. The following chart shows how to program the dipswitches that control system, zone,
and notification appliance operation. Refer to Figure 3-1 for location of the dipswitches.
Important!
When you change a dipswitch, be sure to power down the panel. Dipswitch changes will be
recognized on power up only.
Table 5-1: DIP Switch Programming
Options
Dip Switch
Number
Feature
Switch
Number
Comments
Zone 1 1
Enhanced Mode On 1 On
Enhanced mode. Use when both pull
stations and detectors will be used in the
same zone.
Enhanced Mode Off 1 Off
Normal mode. Use when 2- or 4-wire
smoke detectors and smoke verification
are used in the same zone.
Alarm Verification On 2 On
Alarm Verification
Note:
Do not use with smoke
detectors that have verification built-
in.
Alarm Verification Off 2 Off No verification
Zone Types
Fire Zone
3 Off
4 Off
Supervisory Zone
3 On
4 Off
Water Flow Zone No
Delay
3 Off
4 On
Water Flow Zone
With Delay
3 On Refer to “General Options” to program
the Water Flow delay time.
4 On