Installation guide

- 8 - AL602ADA220J
Optional hookups:
1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]to
reportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional
supervisorymonitoring.(see Power Board Parameter for use of AC Delay, pg. 6)
ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 2a)tothe
commontroubleinput.
2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman
addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.
4- ACLocal[NC,NO,C]shouldconnecttothehostcontrolpanelforlocalannunciationof
thetroublecondition.
Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe
shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 2b).
Maintenance:
Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel
(26.2-26.4VDC recommended range).
Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatthe
batteryterminalandattheboardterminalsmarked[+BAT--]toensurethereisnobreakinthebatteryconnectionwires.
Fuses:Checkinputfuseonthepowersupplyboard,replaceifnecessary.Inputfuseratingis5amp@250V.
Note:Maximumchargingcurrentis650mA.
Note:Expectedbatterylifeis5years,howeveritisrecommendedchangingbatteriesin4yearsorlessifneeded.