Installation guide
- 4 - AL602ADA220J
7. Forconnectionofsmokedetectors,digitaldialer(see Hookup Diagram, pg. 7).
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:
• ForallClassB,StyleW,X,Y,hookupsSW1&SW2ontheAL800LGK9Elogicboardmustbeopen.
ForallClassA,StyleZhookupsSW1&SW2ontheAL800LGK9Elogicboardmustbeclosed.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Switch Positions
Descriptions
ON OFF
InputtoOutputFollowerMode 1 2,3
Outputfollowssignalitreceivesfromthecorrespondinginput
(i.e.FACPSyncmodule-maintainssynchronizationof
notificationappliancecircuit).
TemporalCode3Mode 3 1,2
EnablesTemporalCode3signalgenerationoutput.
Thismodewillacceptasteadyorapulsinginput.
SteadyMode 1,2,3
Asteadyoutputsignalwillbegenerated.
Thismodewillacceptsteadyorpulsinginput.
For the above modes Dip Switch 4 determines which Input controls
the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by input 1.
Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1)
and audible notification appliances (horns) via input 2 (IN2). This allows audible
notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. The
FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the
AL602ADA220J (NAC Power Extender) is connected.
Sync Mode Selection Table:
Function
Switch Positions
Descriptions
ON OFF
AmsecoSync
Mode*
1,3,
4
2
ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,and
horn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/
strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Faraday
SyncMode*
2,4 1,3
ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,and
horn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/
strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Gentex
®
SyncMode*
Gentexisaregisteredtrademarkof
GentexCorporation.
1,2,
3,4
ThismodeisdesignedtoworkwiththeGentex
®
seriesofhorns,strobes,and
horn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/
strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
SystemSensor
®
SyncMode*
SystemSensorisaregistered
trademarkofHoneywell.
1,2,4 3
ThismodeisdesignedtoworkwiththeSystemSensor
®
seriesofhorns,strobes,
andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehorns
ofthehorn/strobecombinationoveratwo-wirecircuitwhileleaving
strobesactive.
CooperWheelock
®
SyncMode*
CooperWheelockisa
registeredtrademarkof
CooperWheelock.
2,3,4 1
ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,
andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,
synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehorns
ofthehorn/strobecombinationoveratwo-wirecircuitwhileleaving
strobesactive.
(AL800LGK9E Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC