Installation guide

AL602ADA220J - 3 -
Power Supply Specifications:
AC Input:
220VAC50/60Hz,2amp.
Output:
Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.
One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotal
outputcurrentmustnotexceedcurrent6.5ampinAlarmCondition.
Battery:
Usetwo(2)12VDC/7AH,two(2)12VDC/12AHortwo(2)12VDC/40AH
batteriesconnectedinseries.
Stand-by/Alarm Current
Consumption:
90mA/175mA
EOL Resistor (end of line):
2.2K(2200ohm),AltronixModel#AL-EOL22(included).
Ground fault maximum
test impedance:
1000ohm.
Stand-by Specifications:
Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24VDC/7AH 24Hours 6.5amp/5minutes ---
24VDC/12AH
(usetwo(2)12VDCbatteriesinseries)
24Hours 6.5amp/5minutes 50mA
24VDC/40AH 24Hours 6.5amp/5minutes 1amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power
outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. When
loads are connected to “AUX” output during alarm condition, the remaining outputs may, not exceed 6.5 amp
total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
Installation Instructions:
WiringmethodsshouldbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/
ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.
Productisintendedforindoordryuseonly.
Carefully review:
Application Guide for AL602ADA220J, AL802ADA220J, AL1002ADA220J.
Power Supply Specifications (pg. 3)
Stand-by Specifications (pg. 3)
Output Programming Selection Table (pg. 4)
Sync Mode Selection Table (pg. 4)
Terminal Identification Table (pgs. 5-6)
LED Status Indication Table (pg. 6)
1.Mounttheunitinthedesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe
enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s
upperkeyholesoverthetwoupperscrews;levelandsecure.Markthepositionofthelowertwoholes.Removethe
enclosure.Drillthelowerholesandinstallthetwofasteners.Placetheenclosure’supperkeyholesoverthetwoupper
screws.Installthetwolowerscrewsandmakesuretotightenallscrews(Enclosure Dimensions, pg. 12).
Secureenclosuretoearthground(Fig. 1, pg. 3). Smallterminalblockwiregaugesrangefrom
16AWGto24AWG,allothersrangefrom14AWGto24AWG.
2. Connecttheline(L)andground(G)terminalstoaseparateunswitchedACcircuit(220VAC,50/60Hz)
dedicatedtotheFireAlarmSystem.
3.Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidingpotentialdamage.
4. Connectbatterytotheterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded).
Usetwo(2)12VDCbatteriesconnectedinseries.
5. Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and
desiredoutputsignaltype (Output Programming Selection Table, pg. 4).
6. ConnectFACPoutputtodesiredAL800LGK9Elogicboardinputs,andnotificationappliancestodesired
AL800LGK9Elogicboardoutputs(see 02 Application Guide).
Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith
synchronizationcapability.
Fig. 1
L N
line
ground
neutral