AL602ADA220J NAC Power Extender Installation Guide (see Application Guide for additional information) Rev.
AL602ADA220J - NAC Power Extender Overview: The Altronix AL602ADA220J is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories.
Power Supply Specifications: AC Input: 220VAC 50/60Hz, 2 amp. Output: Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current. One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total output current must not exceed current 6.5 amp in Alarm Condition. Battery: Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH batteries connected in series. Stand-by/Alarm Current Consumption: 90mA/175mA EOL Resistor (end of line): 2.
7. For connection of smoke detectors, digital dialer (see Hookup Diagram, pg. 7). Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings: • For all Class B, Style W, X, Y, hookups SW1 & SW2 on the AL800LGK9E logic board must be open. For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK9E logic board must be closed.
*Note: The AL602ADA220J will only synchronize horns, horn/strobes and strobes that contain synchronization capability. Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be selected for all outputs Amount of Notification Appliances per NAC: Amseco Faraday Gentex® 27 per NAC* 39 per NAC* 32 per NAC* System Sensor® CooperWheelock® 32 per NAC* 32 per NAC* *Not to exceed a maximum of 2.5 amp per NAC.
AL600ADA Power Supply Board* Terminal Identification Table: Terminal Legend L, G, N Function/Description - DC + 24VDC @ 6.5 amp in alarm non power-limited output. Connect 220 VAC to these terminals: L to hot, N to neutral. Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
Hookup Diagram: Fig. 2 CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuse with the same type and rating. Product is intended for indoor dry use only. Do not expose to rain or moisture. NO C N NC C + OUT3 -- + OUT2 -- + OUT1 -- + SW2 SW1 RESET NO "REMOTE" C -- DC + + OUT4 -- 10A unswitched 120VAC power mains (non-power limited) 4-wire Smoke Detector AC Regulated Power-Limited Outputs Supervised 2.
Optional hookups: 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. (see Power Board Parameter for use of AC Delay, pg. 6) To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2a) to the common trouble input.
Battery Calculation Worksheet Device For each device use this formula: Number of Current per Device Devices This column x This column = Equals AL602ADA220J (Current draw from battery) 1 A AL602 Current Auxiliary Devices Stand-by: 90mA Alarm: 175mA 90mA 175mA 90mA 175mA Refer to device manual for current ratings. Alarm/Stand-by Alarm/Stand-by Alarm/Stand-by B Stand-by Alarm Current Current Current per number of devices.
Appendix A - Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with AL602ADA220J AUX output.
A.1 Four (4) Wire Smoke Detectors (cont.) Detector Type Smoke Detector/Base Max Standby Current (mA) .05 .05 .05 .05 Alarm Current (mA) 23 23 35 35 System Sensor 4W-B (12/24 volt) System Sensor 4WT-B (12/24 volt) System Sensor 4WTA-B (12/24 volt) System Sensor 4WTR-B (12/24 volt) Photoelectric I3 Photoelectric I3 w/Therm I3 Photo w/Therm/Sounder I3 Photo w/Therm/Relay System Sensor 4WTR-B (12/24 volt) I3 Photo w/Therm/ Sounder/Relay .
A.4 Strobes Table A-4 below lists strobes compatible with AL602ADA220J NAC output.
A.4 Strobes (cont.) Wheelock Devices: Coded Audible Appliances AMT - 12/24 AMT - 12/24-NYC CH70 CSX10-24-DC MT-12/24 AMT4 - 12/24 AMT4 - 12/24-NYC CH90 CSXG10-24-DC MT4-12/24 Non-Synchronizing Appliances MB-G6-12 MB-G10-12 MIZ-TC12 MB-G6-24 MB-G10-24 MIZ-TC24 Gentex Devices: Models GE3 Series SSPK Wall and Ceiling Mount Series GES/GEC Series GCS/ GX93 Series GCC Series WGE and color lense units.
A.4 Strobes (cont.
Notes: AL602ADA220J - 15 -
Enclosure Dimensions (H x W x D approximate): 18” x 14.5” x 4.5” (457.2mm x 368.3mm x 114.3mm) 14.5” (368.3mm) 1.5” (38.1mm) 2.5” (63.5mm) 2.5” (63.5mm) 1.5” (38.1mm) 4.5” (114.3mm) 1.0” (25.4mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.25” (31.75mm) 1.5” (38.1mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.5” (38.1mm) 2.5” (63.5mm) 8.5” (215.9mm) 6.0” (152.4mm) 18.0” (457.2mm) 18.0” (457.2mm) 18.0” (457.2mm) 1.0” (25.4mm) 1.0” (25.4mm) 1.0” (25.4mm) 2.75” (69.85mm) 1.5” (38.1mm) 14.5” (368.3mm) 4.5” (114.