Instruction manual
P83567 C
Sheet 5 of 10
Table 3C: Vertical Plane (Ceiling Mount)
Vertical 15C 30C 75C 100C
Angle
(in deg.)
UL
Min.
Typ.
15C
UL
Min.
Typ.
30C
UL
Min.
Typ.
75C
UL
Min.
Typ.
100C
0 15.0 21 30.0 42 75.0 90 100 132
5 13.5 20 27.0 40 67.5 92 90 129
10 13.5 20 27.0 40 67.5 89 90 127
15 13.5 20 27.0 40 67.5 86 90 121
20 13.5 20 27.0 40 67.5 86 90 116
25 13.5 20 27.0 40 67.5 83 90 109
30 11.3 19 27.0 38 67.5 77 75 113
35 11.3 17 19.5 34 48.8 70 75 100
40 11.3 17 13.8 34 34.3 65 75 96
45 11.3 15 10.2 30 25.5 62 75 92
50 18.3 10 8.1 20 20.0 42 55 86
55 6.8 8 6.6 16 16.3 35 45 79
60 6.0 8 5.4 16 13.5 33 40 76
65 5.3 8 4.8 16 12.0 31 35 59
70 5.3 8 4.5 16 11.3 31 35 45
75 4.5 8 4.0 16 10.0 31 30 43
80 4.5 7 3.6 14 9.0 30 30 42
85 3.8 7 3.6 14 9.0 27 25 41
90 3.8 6 3.6 13 9.0 26 25 36
WIRING INFORMATION:
1. Each doubling of rated Watts increases sound output by 3 dBA. Field selectable input terminals are provided on each unit. The
following wattage selections are available: 1/8W, 1/4W, 1/2W, 1W, 2W, 4W, and 8W. Frequency range of speakers is 400-
4000Hz.
2. A 10
ยต
F blocking capacitor for DC supervision of audio lines by the FACP is factory wired in series with the speaker input.
Figure 1. Figure 2.
+ STROBE - COM+
(OPTIONAL)
FROM PRECEDING SPEAKER
OR FIRE ALARM
CONTROL PANEL (FACP)
FROM PRECEDING STROBE
APPLIANCE OR SYBC MODULE
TO NEXT APPLIANCE
OR EOLR
TO NEXT SPEAKER
OR END-OR-LINE RESISTOR
(EOLR)
1. Low Profile Series E Speaker and Series E
Speaker Strobe models have in-out wiring
terminals that accept two #12 to #18 American
Wire Gauge (AWG) wires at each screw
terminal. Strip leads 3/8 inches and connect to
screw terminals.
2. Break all in-out wire runs on supervised circuits
to assure integrity of circuit supervision as
shown in Figure 2. The polarity shown in the
wiring diagrams is for operation of the
appliances.
* Refer to Sync Module instruction sheets SM (P83123) and DSM
(P83177) for additional information.