Instruction manual

P83567 C
Sheet 3 of 10
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL
INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY
AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM AND DSM SYNC MODULES DO NOT EXCEED THE
POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO
WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS
COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total average, peak and inrush currents: Use Table 2 (for wall mount) and 2A (for ceiling mount) to determine
the highest value of “Rated Average Current” for an individual strobe (across the expected operating voltage range of the strobe), and
the highest value of “Rated Inrush Current” or “Rated Peak Current” (whichever is higher) of an individual strobe (across the
expected voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any
other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies
may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of
power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or
lack of battery backup across the output) may exhibit this characteristic.
CAUTION:
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
LIGHT DISTRIBUTION:
Table 3: Horizontal Plane (Wall Mount)
Horizontal 15W 1575W* 30W 75W 110W
Angle
(in deg.)
UL
Min.
Typ.
15W
Typ.
1575W
UL
Min.
Typ.
30W
UL
Min.
Typ.
75W
UL
Min.
Typ.
110W
0 15.0 24 94 30.0 46 75.0 103 110.0 149
5 13.5 24 93 27.0 46 67.5 103 99.0 152
10 13.5 24 88 27.0 45 67.5 104 99.0 151
15 13.5 24 87 27.0 46 67.5 100 99.0 151
20 13.5 23 85 27.0 43 67.5 101 99.0 148
25 13.5 23 80 27.0 43 67.5 98 99.0 140
30 11.3 21 75 22.5 41 56.3 94 82.5 135
35 11.3 20 71 22.5 40 56.3 89 82.5 129
40 11.3 19 62 22.5 39 56.3 83 82.5 124
45 11.3 18 52 22.5 41 56.3 81 82.5 133
50 8.3 18 35 16.5 36 41.3 77 60.5 121
55 6.8 12 32 13.5 27 33.8 60 49.5 85
60 6.0 11 34 12.0 30 30.0 59 44.0 95
65 5.3 13 27 10.5 35 26.3 71 38.5 113
70 5.3 17 19 10.5 29 26.3 73 38.5 81
75 4.5 13 11 9.0 22 22.5 53 33.0 72
80 4.5 8 9 9.0 17 22.5 35 33.0 50
85 3.8 7 10 7.5 15 18.8 30 27.5 38
90 3.8 6 10 7.5 15 18.8 30 27.5 43
* 1575W models are UL Listed for 15cd and meet 75cd on axis.