FLOW CHART OF SUGGESTED TUNING PROCEDURES
System Defaut
Weak Performance & or False alarms
from your systems or theirs
Chec k Nois e "D"
D B
Alternate betw een D1-D2 & B to
get most favorable parameters
( Low Noise Level )
If noise is less than 80 If noise is very high (eg. more than hundreds)
H A
If OK - You are done If noise is very high
1/2 of new noise or less=value than several hundred
inc rease s lightly if False A larms Adjust Gain to 0
IF Not Acceptable
Check Noise Value and
Sensitivity of the System .
C H
If system is picking w ell,
Adjust until sensitive enough Your'e Done, If w eak
then increase until stable adjust H to approximately
1/2 of Noise Level, if f alse
alrarms adjust slightly
Upw ar d
C
Adjust from C6 to C1
until system is w orking
w ell. Than adjust Up
until system is stable
*Alw ays Watch the system f or about an Hour to ensure that you have chosen stable paramaters