Specifications
10/31/02 Tech-304/DWO 14195 Page 28 of 39
Section 6 - Specifications
Input
Signal: 4 to 20 mA, two wire
Voltage: 12.3 Volts DC
Pressure: 15 - 45 psi (Low)
40 - 120 psi: (High)
Output
Flow Rate: 8.0 scfm @ 25 psi (Low)
16.2 scfm @ 90 psi (High)
Pressure: 0 to 45 psi (Low)
0 to 120 psi (High)
Actuator: Single Acting or
Double Acting
Technical
Resolution: .2% Full Travel
Linearity: .5% Full Scale (Rotary)
1% Full Scale (Linear)
Hysteresis: .2% Full Scale
Repeatability: .2% Over One Hour
Operating Temp: -40°C to 85°C
(-40°F to 185°F)
Thermal Coefficient: 2% / 100°C
Air Consumption: .003 scfm @ 25 psi (Low)
.008 scfm @ 90 psi (High)
Hazardous Rating: Non-Incendive,
Class I, Division 2,
Groups A,B,C,D
Class II, Division 2,
Groups F,G
Class III, Division 2
Intrinsically Safe
Class I, Division 1,
Groups A,B,C,D
Class II, Division 1,
Groups E,F,G
Class III, Division 1
Stroke: .25 to 24 inches (Linear)
0 to 95 Degrees (Rotary)
Position Feedback: Magnetic (Non-Contact)
Diagnostics: HART Protocol, Software
Utilizing HART Protocol
Enclosure
Material: Engineered Resin
Class of Equipment: NEMA type 4
Weight: 7.2 Pounds
Air Connections: 1/4” NPT
Conduit Connection: 1/2” NPT (Standard)
M20 (Optional)
Approvals FM, CSA (Standard)
Cenelec (Special Label Req.)
Kema (Special Label Req.)