4.3 Automatic Calibration
The Automatic Calibration (ACAL) performs several self-adjustments, as well as a zero calibration, a span
calibration, and tunes the positioners PID gain settings. Enter and start the Automatic Calibration from the
Menu level. From the menu level press the down arrow button until ACAL is shown on the display (ACAL
Routine Shown Below).
4.4 Proceed to Exiting Calibration or Perform Advanced Calibration
At this point the calibration of the positioner is complete. The Automatic Calibration that was performed in
Section 3 is adequate for most applications. If no advanced calibration is required proceed to Section 5 to
exit calibration. If the user requires to use the advanced settings to fine tune the positioner he may proceed
with the remainder of this step and perform adjustments and calibrations in the Manual Calibration Menu
(MCAL). From the menu level press the down arrow button until MCAL is shown on the display (MCAL
Routine shown below).
ACAL
Set 12mA
Press CAL Key
Auto Calibrate
1. Sensor Cal
2. Trnd
3. Lo
4. Hi
Down Arrow
(From Previous Menu)
Up Arrow
(Exit Calibration)
Down Arrow
(To Next Menu)
5. Auto PID
Down
Arrow
MCAL
Set mA
for Fail Position
Optional:
Press CAL Key
When Complete
-Lo-
Press CAL Key
Up Arrow
CAL
Up Arrow
-Hi-
Down
Arrow
PID
Down
Arrow
Down
Arrow
Select Arbitrary
Zero Using Up
& Down Arrow
Keys
Press CAL Key
ICAL
Press CAL Key
ICAL
Adjust using
Up & Down
Arrow Keys
(1-5)
Press CAL Key
When Complete
Up Arrow
Down Arrow
(From Previous Menu)
Down Arrow
(To Next Menu)
Up Arrow
(Exit Calibration)
PCAL
Adjust using
Up & Down
Arrow Keys
(1-20)
Snsr
Sensor
Calibration
Press CAL Key
Set 12 mA
Down
Arrow
Trnd
Transducer
Calibration
Down
Arrow
Press CAL Key
Set 12 mA
Up Arrow
-mA-
Set 4.0 mA
Down
Arrow
Press CAL Key
Up Arrow
Press CAL Key
Set 20.0 mA
Press CAL Key
Xmr
Press CAL Key
Read Transmitter
Press CAL Key
Down
Arrow
Value & Use
Up & Down
Arrows to Enter The
Present Zero Value
Use Up & Down
Arrows to Enter
the Desired Zero
Current, Typically
4.0 mA
Use Up & Down
Arrows to Enter
the Desired Span
Current, Typically
20.0 mA
Up Arrow
Press CAL Key
Press CAL Key
Press CAL Key
When Complete
Press CAL Key
Zero
Calibration
Set mA
for Fail Position
Optional:
Press CAL Key
When Complete
Press CAL Key
Select Arbitrary
Span Using Up
& Down Arrow
Keys
Press CAL Key
Span
Calibration
MAN
Automatic
PID Routine
AUT
Down
Arrow
Down
Arrow
Read Transmitter
Value & Use
Up & Down
Arrows to Enter The
Present Span Value
ON
ICAL
OFF
Press CAL Key
Press CAL Key
Press CAL Key
DCAL
Adjust using
Up & Down
Arrow Keys
(1-20)
Press CAL Key
Press CAL Key
Down
Arrow