Specifications
10/31/02 Tech-304/DWO 14195 Page 12 of 39
3.3 Mounting Positioner on a Linear Actuator
Step 1. Mount the magnet assembly to the stem of the actuator. A coupler block normally is
needed to extend the magnet assembly outside the yoke area and into the sensing range of the
magnetic pick-up unit.
Step 2. Fasten the mounting bracket to the actuator.
Step 3. Mount the positioner to the mounting bracket. The positioner should be mounted so the
magnetic pick-up unit of the positioner is centered between the limits of the magnetic assembly’s
stroke. After mounting the positioner, the magnet assembly should be within 1/8” from the back
of the positioner (1/16” is ideal), (See Figure 3-5).
1/16”
Magnet Assembly
ICoT Assembly
Housing
Centerline of
Magnetic
Pick-Up Unit
(Position Sensor)
Actuator
Centerline
Location of Centerline
Lower Limit of Travel
Upper Limit of Travel
Actuator Split Block
(At Upper Limit of Travel)
Actuator Split Block
(At Lower Limit of Travel)
Full
Stroke
Stroke/2
Stroke/2
Figure 3-5
Actuator Yoke
Actuators Split Block
Magnet Assembly
ICoT Assembly
Mounting Bracket
Magnetic Pick-Up
Unit (Position Sensor)
.062
Note: For Fisher actuators model 657 & 667 sizes 34 thru 70, Westlock Controls can supply a
slotted mounting kit design. This will allow the user to easily center the positioner sensor
between the limits of the magnet assembly’s stroke.