Specifications

WESTLOCK CONTROLS CORPORATION
280 MIDLAND AVENUE, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913
www.westlockcontrols.com
1/12/10 TECH-439/D.W.O. 19024 Page 5 of 58
1. Introduction
1.1 Product Certification.
IEC Ex FMG
06.0002x
Ex ia IIC T4
II 1 G
Ex ia IIC T4
II 1G
FM09 ATEX 0028
II3 DT 75~C
nnnn
Ex ia IIC T4
CLASS
I DIV 1 GROUP A, B, C, D
CLASS
II DIV 1 GROUP E, F, G
NI CLASS I DIV 2 GROUP A, B, C, D
This product is designed for use in intrinsically safe systems when connected
through the correct barriers.
1.2 Warnings
Never remove enclosure cover or make/break electrical connections
with power connected to the unit.
Perform all wiring in accordance with site and local codes and the
National Electric Code ANSI-NFPA-70 (US) or the Canadian Electric
Code Part I (Canada) for the appropriate area classifications.
Confirm that the ICOT model being installed is approved for the
hazardous area (consult unit identification label).
Ensure that approved and properly sized IS barriers are used in
installations with IS approved ICOTS (confirm entity parameters from
product ID label).
Confirm that power supplied to unit is within rated specifications listed
on the unit identification label.
Protect the unit from exposure to aggressive substances or
atmospheres to ensure that hazard rating is not compromised.
Disconnect power to and the inlet air supply before conducting any
service or maintenance. Avoid the introduction of any contaminants
into the manifold/valve assembly.
1.3 Description of ICoT Positioner.
The ICoT Smart Valve Positioner is an electro-pneumatic servo system that
continuously controls the position of a valve based on a 4 to 20 mA input signal.
The ICoT is an instrument that derives its power directly from a control systems
current loop. The instrument senses valve position via a non-contact Hall effect
sensor and controls valve position through a current to pressure transducer.