Message Meaning Solution
Input
pressure
unstable
Pressure was
unstable during
calibration
Check:
Pressure supply stability
Actuator and tubing leaks
Manifold and transducer assembly are tightly coupled to the
enclosure and there are no leaks
Check if the cable between the inner canister and the
pneumatic transducer assembly is tightly connected
Actuator/Valve assembly integrity
Perform a full auto CAL
Call factory for additional support
HALL span
too small
Hall sensor
used to read
position is
unstable
Check:
Hall sensor connector and cable, especially if remote (see
Figure 3-4, connector J8)
Magnet assembly:
o For rotary magnets check if it is not rotated 90
degrees (see figures 3.2, 3.3 and 3.4).
o For linear magnets, check if the magnet assembly
center is matching the actuator mid position (see
figures 3.5, 3.6 and 3.7)
Remove power for at least 1 minute, perform a factory default
(see Appendix I) and retry the calibration
Grounding issues, cable shield is properly grounded;
positioner ground is properly connected to a clean ground
reference.
Sources of electromagnetic noise too close to the sensor or to
the positioner cables, like AC cables for motors, inverters etc
Try to replace the Hall sensor and/or the magnet
Call factory for additional support
A2D span
too small
One or more of
the analog
variables
(position,
pressure or loop
current) does
not have
enough span to
calibrate
accordingly
Check:
Hall sensor connector and cable, especially if remote (see
Figure 3-4, connector J8)
Magnet assembly:
o For rotary magnets check if it is not rotated 90
degrees (see figures 3.2, 3.3 and 3.4).
o For linear magnets, check if the magnet assembly
center is matching the actuator mid position (see
figures 3.5, 3.6 and 3.7)
Set-point stability, current generator, grounding issues, cable
shield is grounded properly, cables entry ground is properly
connected to a clean ground reference.
Pressure supply stability, actuator and tubing leaks
Remove power for at least 1 minute, perform a factory default
(see Appendix I) and retry a full auto CAL
Grounding issues, cable shield is properly grounded;
positioner ground is properly connected to a clean ground
reference.
Sources of electromagnetic noise too close to the sensor or to
the positioner cables, like AC cables for motors, inverters etc
Call factory for additional support