Figure3-12
3.7 Setting of switches on a rotary ICoT
1. Operate the actuator to the desired extreme.
2. Loosen magnetic trigger bolt #1. (See Figure 3-13)
3. Slide trigger bolt #1 beneath the first switch and tighten with wrench.
4. Operate the actuator to the opposite extreme.
5. Loosen magnetic trigger bolt #2.
6. Slide trigger bolt #2 beneath the second switch and tighten with wrench.