Specifications

2.5 DeviceNet Cabling Information
Correct termination of the trunk and total trunk and drop limits for the baud rate
the network is to run at must be observed or unreliable operation may result.
Table 7
Maximum Distance
Data Rate Flat Cable Thick Cable Med. & Thin Cable
125 kbd 420m (1378’) 500m (1640’) 100m (328’)
250 kbd 200m (656’) 250m (820’) 100m (328”)
500 kbd 75m (246’) 100m (328’) 100m (328’)
Table 8
Data Rate Maximum Cumulative Drop Length
125 kbd 156m (512’)
250 kbd 78m (236’)
500 kbd 39m (128’)
2.6 DeviceNet Supported Topologies
Figure 14
Tech-309
2-9