Full Product Manual
30 | Westinghouse Outdoor Power Equipment, LLC
TROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSE CORRECTION
Engine will not start
Battery switch in the OFF position. Turn battery switch to the ON position.
Out of fuel. Refuel.
Bad fuel, generator stored without treating or
draining gasoline, or refueled with bad gasoline.
Drain the fuel tank. Refuel with fresh gasoline.
Dirty air lter. Clean the air lter.
Low engine oil level stopped generator.
If low oil LED illuminated, turn battery switch to the OFF
position. Add engine oil.
Spark plug wet with fuel (ooded engine).
Wait ve minutes. Turn battery switch to the OFF
position. Pull recoil handle rapidly several times. If the
generator does not start, remove spark plug and dry.
Spark plug faulty, fouled, or improperly gapped. Gap or replace the spark plug. Reinstall.
Fuel lter restricted, fuel system malfunction, fuel
pump failure, ignition malfunction, valves stuck, etc.
Contact Westinghouse customer service toll-free at 1
(855) 944-3571.
Battery drained.
Use the recoil handle to start the generator.
Charge the battery.
Choke partially open or closed due to weak or
disconnected battery.
Manually set the choke. See Maintenance section.
CO sensor removed or modied. Return to original conguration.
CO sensor activated or system fault occurred.
Relocate generator / Contact Westinghouse customer
service toll-free at 1 (855) 944-3571.
Engine starts, then shuts down
Out of fuel. Refuel.
Incorrect engine oil level. Check engine oil level.
Dirty air lter. Clean the air lter.
Contaminated fuel. Drain the fuel tank. Refuel with fresh gasoline.
Defective low oil level switch.
Contact Westinghouse customer service toll-free at 1
(855) 944-3571.
Engine lacks power
Air lter restricted. Clean or replace air lter.
Bad fuel, generator stored without treating or
draining gasoline, or refueled with bad gasoline.
Drain the fuel tank. Refuel with fresh gasoline.
Fuel lter restricted, fuel system malfunction, fuel
pump failure, ignition malfunction, valves stuck, etc.
Contact Westinghouse customer service toll-free at 1
(855) 944-3571.
Engine runs rough or bogs
when load applied
Dirty air lter. Clean the air lter.
Generator overloaded. Unplug some devices.
Faulty power tool or appliance.
Replace or repair tool or appliance. Stop and restart the
engine.
Fuel lter restricted, fuel system malfunction, fuel
pump failure, ignition malfunction, valves stuck, etc.
Contact Westinghouse customer service toll-free at 1
(855) 944-3571.
No power at AC receptacles
OUTPUT READY LED is OFF and OVERLOAD LED
is ON.
Check AC load. Stop and restart engine.
Check the air inlet. Stop and restart the engine.
AC circuit breaker/s tripped. Check AC loads and reset circuit breaker/s.
Faulty power tool or appliance.
Replace or repair tool or appliance. Stop and restart the
engine.
Faulty generator.
Contact Westinghouse customer service toll-free at 1
(855) 944-3571.