Instruction manual
Primary
Line FU-4 Secondary Secondary
Voltage Connection Connection Jumper Voltage
208 VAC H5 X3 H1 to H3 and H2 to H5 110 VAC
380 VAC H4 X3 H2 to H3 120 VAC
415 VAC H5 X3 H2 to H3 120 VAC
460 VAC H4 X2 H2 to H3 115 VAC
230 VAC H4 X2 H1 to H3 & H2 to H4 115 VAC
The primary to FU-3 is factory connected to H1.
One secondary lead is factory connected to X1.
The X1 and H1 connections remain the same for all line voltages.
Easy-Start ES Instruction Manual
Options
SECTION 4
4-3
Available Options
Cat. No. Suffix Description
T2 300VA control power
transformer. Other details
T4 500VA control transformer.
Other details same as T.
Y2 Time delay relay, (type TR)
delay on make.
Programmable Time
Settings:
1, 3, 6, 10, 60 seconds
5, 10 minutes
Y3 Auxiliary relay, contacts
and coil unwired.
Control Devices:
Cutler-Hammer Transformer Connections
Cat. No. Suffix
Description
T 150VA control power
transformer with 2 primary
fuses.
Easy-Start ES models have multi-voltage ratings.
Each model is factory wired for the following
incoming line voltage for Cutler-Hammer
transformer:
Easy-Start ES
V
oltage Rating CPT Wired For
208/230/460 460V
380/415 380V
If the incoming line voltage is different than the
one shown in above table, reconnect the CPT
primary and secondary as follows for Cutler-
Hammer transformers:
Easy ES-052
Volts
Connect
X2
X1
460
230
H2 to H3
H1 to H3 & H2 to H4
H1-H4
H1-H4
X1-X2
115
H1 H3 H2 H4
Diagram 1
Lines
Easy ES-053
Volts
Connect
X3 X2
X1
416
380
208
115
95
H1-H5
H1-H4
H2 to H3
H2 to H3
H1 to H3 & H2 to H4
H1 to H3 & H2 to H5
H1-H4
H1-H5
X1-X3
X1-X2
H1 H3 H2 H4 H5
Diagram 2
Lines
B