Instruction manual
Easy-Start ES Instruction Manual
Pre-Installation
INSTALLATION
2-12
Application Considerations
Model Number ES250 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 120 180 240 300
250% 625
5 50 70 100 120
10 25 40 50 60
20 12 20 24 30
2 80 120 160 220
300% 750
5 40 60 80 100
10 20 30 40 50
20 10 15 20 25
2 60 90 120 140
400% 1000
5 24 35 50 60
10 12 16 20 30
20 4 8 12 15
2 30 50 70 100
500% 1250
5 16 20 30 35
10 8 10 15 20
20 2 4 6 8
Starts-Per-Hour ES250
Table 2-5
Model Number ES260 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 120 180 240 300
250% 650
5 40 60 100 120
10 20 30 50 60
20 10 15 25 30
2 60 120 160 220
300% 540
5 30 50 70 90
10 12 20 30 40
20 8 12 16 20
2 40 60 100 120
400% 720
5 20 30 40 50
10 8 12 16 24
20 4 6 8 12
2 20 40 60 80
500% 900
5 8 12 20 30
10 4 8 12 16
20 - 2 4 6
Starts-Per-Hour ES260
Table 2-6