Instruction manual

Easy-Start ES Instruction Manual
Pre-Installation
INSTALLATION
2-11
Application Considerations
Model Number ES120 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 120 180 240 360
250% 300
5 70 90 120 150
10 30 50 60 70
20 15 20 25 30
2 100 120 180 240
300% 360
5 40 60 80 100
10 20 30 40 50
20 10 16 20 24
2 60 80 100 120
400% 750
5 30 40 50 60
10 4 8 16 20
20 - 2 4 6
2 12 20 40 50
500% 600
5 8 12 20 24
10 - 2 4 6
20 - - - 1
Starts-Per-Hour ES120
Table 2-3
Model Number ES180 Starts-Per-Hour
Curr. Starting Start Percent Off-Time
Limit Current Time
AC Amps Sec. 0% 10% 20% 30%
2 100 160 240 300
250% 450
5 40 60 80 100
10 20 30 45 60
20 10 15 20 30
2 80 120 180 220
300% 540
5 30 40 60 80
10 12 20 30 40
20 8 10 12 16
2 40 60 90 120
400% 720
5 20 30 40 50
10 8 12 16 20
20 4 8 10 12
2 24 40 80 100
500% 900
5 12 20 30 40
10 4 8 12 16
20 - 2 4 6
Starts-Per-Hour ES180
Table 2-4