Specifications

EV Inverter Operating Manual
___________________________________________________________________________
TECO Westinghouse Motor Company 63
Models: JNEV 202/203/401/402/403 H3FN4S (IP65) Installation
REV 0 FWD
Switch
Potentiometer
L1(L)
FWD
REV
+24V
0V
AIN
+10V
L2(N)
(PE)
EV
IM
(PE)
T1
T2
T3
Notes:
1. Input source: 1Ø (L1(L), L2(N), PE) must be
connected to a 200 -240VAC or 3Ø (L1(L),
L2(N), L3, PE) must be connected to a 200 -240,
380-480 VAC supply.
2. Motor output: 3Ø (T1-T2-T3, PE).
CAUTION-
- Do not start or stop the drive using the main
input power.
- For the JNEV-202 to 403 H3FN4S type,
set the REV 0 FWD switch to 0 position
so that the drive has no run signal before
power- up. Otherwise injury may result.
- For the JNEV-202 to 403 H3FN4 type,
set the RE or FW switch to the 0FF position
so that the drive has no run signal before
power- up. Otherwise injury may result.
L1 L2
100 120 VAC
50 / 60 Hz, 1Ø
(PE)
(PE)
123.4mm
198.9mm
4.86in.
7.83in.
4-M4
Fig. B.4 JNEV NEMA4 Wiring Diagram
T1 T2 T3
3 Phases
IM
220-240V
380-480V
Single/ThreePhases
DATA
FUN
D SP
E NT
RUN
RESET
S TOP
REV-0-FWD
SWITCH
Potentiometer
POWER
SWITCH
L1(L) L2(N) L3
Notes:
1. Power switch, REV -0 FWD switch and Potentiometer are only
for for the models JNEV 202 - 403 H3FN4S.
2. Power supply cable :JNEV-200 #12 AWG (3.5mm2).
JNEV-200 #16 AWG (1.25mm2)
3. Motor cable: JNEV-200 #14 AWG (2.0m)
JNEV-200 #16 AWG (1.25m)
4. Tightening torques:
- Power / motor cable plug-in terminal block (TM1): 6.94 lb-in.
(8 kgf-cm)
- Control wiring terminal block (TM2): 3.47 lb-in. (4 kgf-cm)
- Outer cover screws (M4): 6.94 lb-in. (8 kgf-cm)
1Ø / 3Ø
(PE)
(PE)
Potentiometer
REV - 0 - FWD
Switch
210.0 mm
275.5 mm
8.27 in.
10.85 in.
(4) M4
IM
Power Switch
L3
Fig. B.3 JNEV NEMA4 Installation and Mounting
AC Input
200 240 VAC
Or
380 480 VAC
50 /60 Hz 1Ø, 3Ø
TM2 401/402/403
RA RB 24V S1 S2 S3 S4 COM 10V AIN COM FM+
red
black
brown
orange
yellow
green
FM+ COM AIN 10V COM S3 S2 S1S4 24V RB RA
green
yellow
orange brown
black
red
TM2 202/203
Foot Print