Specifications

EV Inverter Operating Manual
___________________________________________________________________________
TECO Westinghouse Motor Company 38
2) F11 - F15=005: Jog Frequency Command
The external input terminal set to Jog operation. When turned ON, the inverter will run at the Jog
frequency, F36.
Parameter
Description
Frequency range
Factory default
F28
Preset frequency 1 (Hz)
00.0 - 200
05.0
F29
Preset frequency 2 (Hz)
00.0 - 200
05.0
F30
Preset frequency 3 (Hz)
00.0 - 200
10.0
F31
Preset frequency 4 (Hz)
00.0 - 200
20.0
F32
Preset frequency 5 (Hz)
00.0 - 200
30.0
F33
Preset frequency 6 (Hz)
00.0 - 200
40.0
F34
Preset frequency 7 (Hz)
00.0 - 200
50.0
F35
Preset frequency 8 (Hz)
00.0 - 200
60.0
F36
Jog frequency (Hz)
00.0 - 200
05.0
Set frequency priority: Jog→ Preset frequency →External analog frequency signal
Preset
Frequency
Command 3
Set value =004
Preset
Frequency
Command 2
Set value =003
Preset
Frequency
Command 1
Set value =002
Jog frequency
Command
Set value =005
Output
frequency
0
0
0
0
F28
0
0
1
0
F29
0
1
0
0
F30
0
1
1
0
F31
1
0
0
0
F32
1
0
1
0
F33
1
1
0
0
F34
1
1
1
0
F35
X
X
X
1
F36
X = 1 or 0
F37 DC braking time (s) : 00.0 - 25.5
F38 DC braking start frequency (Hz) : 01.0 - 10.0
F39 DC braking level (%) : 00.0 - 20.0% (Level 100% based on Motor Rate Voltage F44)
NOTE: DC braking is enabled / disabled by multifunction input setting as described on page 33
F37 / F38: DC braking time and start frequency, per the following figure:
F38
HZ
t
F37
Fig. 11.7 DC Injection Braking
t
t
F38
HZ
TM2
DC
Brake
Signal
F11
F15=019