Specifications

EV Inverter Operating Manual
___________________________________________________________________________
TECO Westinghouse Motor Company 24
C41
Local/Remote frequency
control select
(Run command by the
Run/Stop key)
000
UP/Down key on keypad
sets frequency
000
001
Potentiometer on the
keypad set frequency
C42
C43
Terminal S5 function
Terminal S6 function
Note: Terminals S5 and S6
are provided by an SIF-IO
option card.
000
Forward
007
009
001
Reverse
002
Preset speed command 1
003
Preset speed command 2
004
Preset speed command 3
005
Jog frequency command
006
Emergency stop (E.S.)
007
Base block (b.b.)
008
Select 2
nd
acceleration /
deceleration time
009
Reset
010
Up command
011
Down command
012
Control signal switch
013
Communication control
signal switch
014
Acceleration / deceleration
prohibit
015
Master / Auxiliary speed
source select
016
PID Function disable
017
Analog signal input
(terminal AIN)
Not used
with S5 and
S6
018
PID Feedback signal
(terminal AIN)
019
DC Injection brake signal
C44
Multi-function input terminals
S1-S6 signal scan time
(mSec ×8)
-
001 - 100
010
C45
AIN signal scan time
(mSec x 8 )
-
001 - 100
050