Specifications

EV Inverter Operating Manual
___________________________________________________________________________
TECO Westinghouse Motor Company 23
C30
PID operation mode
000
PID PID Function disabled
000
001
PID Control, bias D control
002
PID Control, feedback D
control
003
PID Control, bias D reverse
characteristics control.
004
PID Control, feedback D
reverse characteristics
control.
C31
PID Error gain
-
0.00 10.0
1.00
Note 1
C32
P: Proportional gain
-
0.00 10.0
01.0
Note 1
C33
I: Integral time (sec.)
-
00.0 100
10.0
Note 1
C34
D: Differential time (sec.)
-
0.00 10.0
0.00
Note 1
C35
PID Offset
000
Positive direction
000
Note 1
001
Negative direction
C36
PID Offset adjust (%)
-
000 109
000
Note 1
C37
PID Update time (sec.)
-
00.0 - 02.5
00.0
Note 1
C38
PID Sleep mode threshold (Hz)
-
00.0 - 200
00.0
C39
PID Sleep delay time (sec.)
-
00.0 - 25.5
00.0
C40
Frequency Up/Down
control using MFIT
000
UP/Down command is
available. Set frequency is
held when inverter stops.
000
001
UP/Down command is
available. Set frequency
resets to 0Hz when inverter
stops.
002
UP/Down command is
available. Set frequency is
held when inverter stops.
Up/Down is available
when stopped.