Section 10 - Parameters F (Basic) and C (Advanced) Function Tables
Overview The EV Inverter Series is program capable to allow for a variety of application
requirements. The parameters are split into two categories, F and C. The F parameters set the
Basic functions of the inverter while the C parameters control the more Advanced functions.
The parameters can be accessed and changed through the keypad. (Refer to Sec.9 for keypad
functions and navigation). They may also be accessed and changed though MODBUS protocol in
conjunction with an optional communications module (Refer to Sec. 2 for available
communication options).
When the inverter is shipped from the factory each parameter is set at a Factory Default value
and is so specified in the Tables. Most parameters may not be changed when the inverter is in
the RUN mode. Those parameters that can be are so noted (note 1) in the Remarks column.
Table 10.1 F (Basic) Parameters
F
Parameter
Code
Range/ Function
Factory
Default
Remarks
F00
Inverter horsepower capacity
code
-
Note 5
F01
Acceleration time 1 (sec.)
-
00.1 999
05.0
Note 1 & 2
F02
Deceleration time 1 (sec.)
-
00.1 999
05.0
Note 1 & 2
F03
Motor rotation direction
000
Forward
000
Note 1
001
Reverse
F04
Run command source
000
Keypad
000
001
External terminal
002
Communication control
F05
Frequency command
source
000
UP/Down key on keypad
000
001
Potentiometer on keypad
002
AIN (input signal from TM2)
003
Multi-function input terminal
UP/DOWN function
004
RS-485 Communication
frequency setting
F06
External control operation
mode
000
Forward / Stop -
Reverse / Stop
000
001
Run / Stop-
Forward / Reverse
002
3-wireRun / Stop
F07
Frequency upper limit (Hz)
-
01.0 - 200
50.0 / 60.0
Note 2 & 7
F08
Frequency lower limit (Hz)
-
00.0 - 200
00.0