Section 3 - Control Signal Terminal Block Description
RA RB 24V
S1 S2 S3
S4 COM
COM10V AIN/S7
FM+
1 2 3 4
8
5 6
7
9
10
11
12
TM2
Fig. 3.1 Control Terminals Designations
Terminal
No.
Terminal
Designation
Description
1
RA
Multi function digital output
NO contact rated 250V @ 10A
Refer to parameter F21 (000 015) for selecting output functions
2
RB
3
24V
24VDC @ 20mA Max.
- Provides the common point for the multi function digital inputs S1
S4 when SW1 is set to PNP (Source Mode).
- Provides input power for the various option cards when required.
4
S1
Multi function digital input terminals
Refer to parameters F11 F14 (000 016 ,019) for selecting input functions
5
S2
6
S3
7
S4
8
COM
Output common
- Provides a common for both the 10V (terminal 9) and 24V (terminal 3)
sources
- Provides the common point for the multi function digital inputs S1 S4
when SW1 is set to NPN (Sink Mode).
- Provides a common for various option cards
9
10V
10VDC @ 20mA Max.
- Reference voltage supply for an external speed control potentiometer.
10
AIN / S7
Analog or digital
- AIN Analog: When terminal 10 is used as an analog input refer to
parameters F15 (017 & 018), F16 (000-001), F17, F18, F19 (000-001)
and F20 (000-001).
- S7 Digital: When terminal 10 is used as a digital input, parameters
described for multi function digital input terminals S1 S4 apply.
NOTE : Logic level high; => +8V* logic level low level; =< 2V
*Caution! Do not exceed 10V maximum.
11
COM
Output common
- Same as terminal 8
12
FM+
Multi function analog output
0 +10VDC, Refer to parameter F26 (000-005) for output functions.