Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-14
Code
Name
Data setting range
Change when
running
Data
copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
H49
Starting Mode
(Auto search delay time 1)
0.0 to 10.0 s
Y
Y
0.0
Y
Y
Y
Y
*11
H50
Non-linear V/f Pattern 1
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H51
(Voltage)
0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H52
Non-linear V/f Pattern 2
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H53
(Voltage)
0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H54
Acceleration Time (Jogging)
0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H55
Deceleration Time (Jogging)
0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H56
Deceleration Time for Forced
Stop
0.00 to 6000 s
Y
Y
*1
Y
Y
Y
N
H57
1st S-curve acceleration range
(Leading edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H58
2nd S-curve acceleration range
(Trailing edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H59
1st S-curve deceleration range
(Leading edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H60
2nd S-curve deceleration range
(Trailing edge)
0% to 100%
Y
Y
10
Y
Y
Y
N
H61
UP/DOWN Control
(Initial frequency setting)
0: 0.00 Hz
1: Last UP/DOWN command value on releasing the
run command
N
Y
1
Y
Y
Y
N
H63
Low Limiter (Mode selection)
0: Limit by F16 (Frequency limiter: Low) and
continue to run
1: If the output frequency lowers below the one
limited by F16 (Frequency limiter: Low),
decelerate to stop the motor.
Y
Y
0
Y
Y
Y
N
H64
(Lower limiting frequency)
0.0: Depends on F16 (Frequency limiter, Low)
0.1 to 60.0 Hz
Y
Y
1.6
Y
N
N
N
H65
Non-linear V/f Pattern 3
(Frequency)
0.0: Cancel, 0.1 to 500.0 Hz
N
Y
0.0
Y
N
N
N
H66
(Voltage)
0 to 240: Output an AVR-controlled voltage
(for 230 V series)
0 to 500: Output an AVR-controlled voltage
(for 460 V series)
N
Y2
0
Y
N
N
N
H67
Auto Energy Saving Operation
(Mode selection)
0: Enable during running at constant speed
1: Enable in all modes
Y
Y
0
Y
N
Y
N
H68
Slip Compensation 1
(Operating conditions)
0: Enable during ACC/DEC and at base frequency
or above
1: Disable during ACC/DEC and enable at base
frequency or above
2: Enable during ACC/DEC and disable at base
frequency or above
3: Disable during ACC/DEC and at base frequency
or above
N
Y
0
Y
N
N
N
H69
Automatic Deceleration
(Mode selection)
0: Disable
2: Torque limit control with Force-to-stop if actual
deceleration time exceeds three times the
specified one
3: DC link bus voltage control with Force-to-stop if
actual deceleration time exceeds three times the
specified one
4: Torque limit control with Force-to-stop disabled
5: DC link bus voltage control with Force-to-stop
disabled
Y
Y
0
Y
Y
Y
N
H70
Overload Prevention Control
0.00:Follow the deceleration time selected
0.01 to 100.0 Hz/s
999: Cancel
Y
Y
999
Y
Y
Y
N
H71
Deceleration Characteristics
0: Disable 1: Enable
Y
Y
0
Y
N
N
N
H72
Main Power Down Detection
(Mode selection)
0: Disable 1: Enable
Y
Y
1
Y
Y
Y
Y
*1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above.