Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-11
C codes: Control Functions of Frequency
Code
Name
Data setting range
Change when
running
Data copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
C01
Jump Frequency 1
0.0 to 500.0 Hz
Y
Y
0.0
Y
Y
Y
N
4-105
C02
2
Y
Y
0.0
Y
Y
Y
N
C03
3
Y
Y
0.0
Y
Y
Y
N
C04
(Hysteresis width)
0.0 to 30.0 Hz
Y
Y
3.0
Y
Y
Y
N
C05
Multi-frequency 1
0.00 to 500.00 Hz
Y
Y
0.00
Y
Y
Y
N
C06
2
Y
Y
0.00
Y
Y
Y
N
C07
3
Y
Y
0.00
Y
Y
Y
N
C08
4
Y
Y
0.00
Y
Y
Y
N
C09
5
Y
Y
0.00
Y
Y
Y
N
C10
6
Y
Y
0.00
Y
Y
Y
N
C11
7
Y
Y
0.00
Y
Y
Y
N
C12
8
Y
Y
0.00
Y
Y
Y
N
C13
9
Y
Y
0.00
Y
Y
Y
N
C14
10
Y
Y
0.00
Y
Y
Y
N
C15
11
Y
Y
0.00
Y
Y
Y
N
C16
12
Y
Y
0.00
Y
Y
Y
N
C17
13
Y
Y
0.00
Y
Y
Y
N
C18
14
Y
Y
0.00
Y
Y
Y
N
C19
15
Y
Y
0.00
Y
Y
Y
N
C20
Jogging Frequency
0.00 to 500.00 Hz
Y
Y
0.00
Y
Y
Y
N
4-107
C30
Frequency Command 2
0: Enable / keys on the keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals
[12]and [C1]
5: Voltage input to terminal [V2] (-10 to +10 VDC)
7: Terminal command UP/DOWN control
8: Enable / keys on the keypad
(balanceless-bumpless switching available)
11: Digital input interface card (option)
12: Pulse train input
N
Y
2
Y
Y
Y
N
4-26
4-107
C31
Analog Input Adjustment for [12]
(Offset)
-5.0% to 5.0%
Y*
Y
0.0
Y
Y
Y
Y
4-107
C32
(Gain)
0.00% to 400.00%
Y*
Y
100.00
Y
Y
Y
Y
C33
(Filter time constant)
0.00 to 5.00 s
Y
Y
0.05
Y
Y
Y
Y
C34
(Gain base point)
0.00% to 100.00%
Y*
Y
100.00
Y
Y
Y
Y
C35
(Polarity)
0: Bipolar 1: Unipolar
N
Y
1
Y
Y
Y
Y
C36
Analog Input Adjustment for [C1]
(Offset)
-5.0% to 5.0%
Y*
Y
0.0
Y
Y
Y
Y
C37
(Gain)
0.00% to 400.00%
Y*
Y
100.00
Y
Y
Y
Y
C38
(Filter time constant)
0.00 to 5.00s
Y
Y
0.05
Y
Y
Y
Y
C39
(Gain base point)
0.00% to 100.00%
Y*
Y
100.00
Y
Y
Y
Y
C40
Terminal [C1] Range Selection
0: 4 to 20 mA
1: 0 to 20 mA
N
Y
0
Y
Y
Y
Y
C41
Analog Input Adjustment for [V2]
(Offset)
-5.0% to 5.0%
Y*
Y
0.0
Y
Y
Y
Y
C42
(Gain)
0.00% to 400.00%
Y*
Y
100.00
Y
Y
Y
Y
C43
(Filter time constant)
0.00 to 5.00 s
Y
Y
0.05
Y
Y
Y
Y
C44
(Gain base point)
0.00% to 100.00%
Y*
Y
100.00
Y
Y
Y
Y
C45
(Polarity)
0: Bipolar 1: Unipolar
N
Y
1
Y
Y
Y
Y
4-26
4-107
C50
Bias (Frequency command 1)
(Bias base point)
0.00% to 100.00%
Y*
Y
0.00
Y
Y
Y
Y
4-26
4-108
C51
Bias (PID command 1)(Bias value)
-100.00% to 100.00%
Y*
Y
0.00
Y
Y
Y
Y
C52
(Bias base point)
0.00% to 100.00%
Y*
Y
0.00
Y
Y
Y
Y
4-108
C53
Selection of Normal/Inverse
Operation(Frequency command 1)
0: Normal operation
1: Inverse operation
Y
Y
0
Y
Y
Y
Y
4-71
4-108