Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-10
Code
Name
Data setting range
Change when
running
Data copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
30 (1030): Force to stop (STOP)
(30 = Active OFF, 1030 = Active ON)
Y
Y
Y
Y
4-71
4-104
32 (1032): Pre-excitation (EXITE)
N
Y
Y
N
33 (1033): Reset PID integral and differential
components (PID-RST)
Y
Y
Y
N
34 (1034): Hold PID integral component (PID-HLD)
Y
Y
Y
N
35 (1035): Select local (keypad) operation (LOC)
Y
Y
Y
Y
39: Protect motor from dew condensation (DWP)
Y
Y
Y
Y
40: Enable integrated sequence to switch
to commercial power (50 Hz) (ISW50)
Y
N
N
N
41: Enable integrated sequence to switch
to commercial power (60 Hz) (ISW60)
Y
N
N
N
47 (1047): Servo-lock command (LOCK)
N
N
Y
N
49 (1049): Pulse train sign (SIGN)
59 (1059): Enabled battery operation (BATRY)
Y
Y
Y
Y
Y
Y
Y
Y
70 (1070): Cancel constant peripheral speed
control (Hz/LSC)
Y
Y
Y
N
71 (1071): Hold the constant peripheral speed
control frequency in the memory(LSC-HLD)
Y
Y
Y
N
72 (1072): Count the run time of commercial
power-driven motor 1 (CRUN-M1)
Y
N
N
Y
73 (1073): Count the run time of commercial
power-driven motor 2 (CRUN-M2)
Y
N
N
Y
76 (1076): Select droop control (DROOP)
Y
Y
Y
N
77 (1077): Cancel PG alarm (PG-CCL)
N
N
Y
Y
80 (1080): Cancel customizable logic (CLC)
Y
Y
Y
Y
81 (1081): Clear all customizable logic timers (CLTC)
Y
Y
Y
Y
98: Run forward (FWD)
Y
Y
Y
Y
99: Run reverse (REV)
Y
Y
Y
Y
100: No function assigned (NONE)
Y
Y
Y
Y
Setting the value in parentheses ( ) shown above
assigns a negative logic input to a terminal.
Item values in parentheses indicated value for negative logic.
Y: Applicable / N: Not Applicable.