Instruction manual

Table Of Contents
4-9
Code
Name
Data setting range
Change when
running
Data copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
E50
Coefficient for Speed Indication
0.01 to 200.00
Y
Y
30.00
Y
Y
Y
Y
4-100
E51
Display Coefficient for Input
Watt-hour Data
0.000 (Cancel/reset), 0.001 to 9999
Y
Y
0.010
Y
Y
Y
Y
E54
Frequency Detection 3 (Level)
0.0 to 500.0 Hz
Y
Y
60.0
Y
Y
Y
Y
4-101
4-94
E55
Current Detection 3 (Level)
0.00 (Disable);
Current value of 1% to 200% of the inverter rated
current
Y
Y1 Y2
*2
Y
Y
Y
Y
4-101
4-95
E56
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
4-102
E61
Terminal [12] Extended Function
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID command 1
5: PID feedback amount
6: Ratio setting
7: Analog torque limit value A
8: Analog torque limit value B
10:Torque command
11: Torque current command
17: Speed limit FWD
18: Speed limit REV
20: Analog input monitor
N
Y
0
Y
Y
Y
Y
E62
Terminal [C1] Extended
Function
N
Y
0
Y
Y
Y
Y
E63
Terminal [V2] Extended
Function
N
Y
0
Y
Y
Y
Y
E64
Saving of Digital Reference
Frequency
0: Automatic saving (when main power is turned OFF)
1: Saving by pressing key
Y
Y
1
Y
Y
Y
Y
4-103
E65
Reference Loss Detection
(Continuous running frequency)
0: Decelerate to stop, 20% to 120%, 999: Disable
Y
Y
999
Y
Y
Y
Y
E78
Torque Detection 1 (Level)
0% to 300%
Y
Y
100
Y
Y
Y
Y
4-104
E79
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
E80
Torque Detection 2/
Low Torque Detection (Level)
0% to 300%
Y
Y
20
Y
Y
Y
Y
E81
(Timer)
0.01 to 600.00 s
Y
Y
20.00
Y
Y
Y
Y
Selecting function code data assigns the corresponding
function to terminals [FWD] and [REV] as listed below.
4-71
4-104
E98
Terminal [FWD] Function
0 (1000): Select multi-frequency (0 to 1 steps) (SS1)
N
Y
98
Y
Y
Y
N
E99
Terminal [REV] Function
1 (1001): Select multi-frequency (0 to 3 steps) (SS2)
N
Y
99
Y
Y
Y
N
2 (1002): Select multi-frequency (0 to 7 steps) (SS4)
Y
Y
Y
N
3 (1003): Select multi-frequency (0 to 15 steps) (SS8)
Y
Y
Y
N
4 (1004): Select ACC/DEC time (2 steps) (RT1)
Y
Y
Y
N
5 (1005): Select ACC/DEC time (4 steps) (RT2)
Y
Y
Y
N
6 (1006): Enable 3-wire operation (HLD)
Y
Y
Y
Y
7 (1007): Coast to a stop (BX)
Y
Y
Y
Y
8 (1008): Reset alarm (RST)
Y
Y
Y
Y
9 (1009): Enable external alarm trip (THR)
(9 = Active OFF, 1009 = Active ON)
Y
Y
Y
Y
10 (1010): Ready for jogging (JOG)
Y
Y
Y
N
11 (1011): Select frequency command 2/1 (Hz2/Hz1)
Y
Y
Y
N
12 (1012): Select motor 2 (M2)
Y
Y
Y
Y
13: Enable DC braking (DCBRK)
Y
Y
Y
N
14 (1014): Select torque limiter level 2/1 (TL2/TL1)
Y
Y
Y
Y
15: Switch to commercial power (50 Hz) (SW50)
Y
N
N
N
16: Switch to commercial power (60 Hz) (SW60)
Y
N
N
N
17 (1017): UP (Increase output frequency) (UP)
Y
Y
Y
N
18 (1018): DOWN (Decrease output frequency)
(DOWN)
Y
Y
Y
N
19 (1019): Enable data change with keypad (WE-KP)
Y
Y
Y
Y
20 (1020): Cancel PID control (Hz/PID)
Y
Y
Y
N
21 (1021): Switch normal/inverse operation (IVS)
Y
Y
Y
N
22 (1022): Interlock (IL)
Y
Y
Y
Y
23 (1023): Cancel torque control (Hz/TRQ)
N
N
N
Y
24 (1024): Enable communications link via RS-485
or fieldbus (LE)
Y
Y
Y
Y
25 (1025): Universal DI (U-DI)
Y
Y
Y
Y
26 (1026): Enable auto search for idling motor
speed at starting (STM)
Y
Y
N
Y
The shaded function codes are applicable to the quick setup.
*2 The motor rated current is automatically set. See Table B (P03/A17).
Item values in parentheses indicated value for negative logic.
Y: Applicable / N: Not Applicable.