Instruction manual

Table Of Contents
4-7
Code
Name
Data setting range
Change when
running
Data copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
E10
Acceleration Time 2
0.00 to 6000 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start and -stop.
Y
Y
*1
Y
Y
Y
N
4-37
E11
Deceleration Time 2
Y
Y
*1
Y
Y
Y
N
E12
Acceleration Time 3
Y
Y
*1
Y
Y
Y
N
E13
Deceleration Time 3
Y
Y
*1
Y
Y
Y
N
E14
Acceleration Time 4
Y
Y
*1
Y
Y
Y
N
E15
Deceleration Time 4
Y
Y
*1
Y
Y
Y
N
E16
Torque Limiter 2-1
-300% to 300%; 999 (Disable)
Y
Y
999
Y
Y
Y
Y
4-58
E17
Torque Limiter 2-2
-300% to 300%; 999 (Disable)
Y
Y
999
Y
Y
Y
Y
Selecting function code data assigns the corresponding
function to terminals [Y1] to [Y5A/C] and [30A/B/C] as listed
below.
4-88
E20
Terminal [Y1] Function
0 (1000): Inverter running (RUN)
N
Y
0
Y
Y
Y
Y
E21
Terminal [Y2] Function
1 (1001): Frequency (speed) arrival signal (FAR)
N
Y
1
Y
Y
Y
N
E22
Terminal [Y3] Function
2 (1002): Frequency (speed) detected (FDT)
N
Y
2
Y
Y
Y
Y
E23
Terminal [Y4] Function
3 (1003): Undervoltage detected (Inverter stopped) (LU)
N
Y
7
Y
Y
Y
Y
E24
Terminal [Y5A/C]
Function
4 (1004): Torque polarity detected (B/D)
5 (1005): Inverter output limiting (IOL)
N
Y
15
Y
Y
Y
Y
E27
Terminal [30A/B/C]
Function
N
Y
99
Y
Y
Y
Y
(Relay output)
6 (1006): Auto-restarting after momentary power
failure (IPF)
Y
Y
Y
Y
7 (1007): Motor overload early warning (OL)
Y
Y
Y
Y
8 (1008): Keypad operation enabled (KP)
Y
Y
Y
Y
10 (1010): Inverter ready to run (RDY)
Y
Y
Y
Y
11: Switch motor drive source between
commercial power and inverter output
(For MC on commercial line) (SW88)
Y
N
N
N
12: Switch motor drive source between
commercial power and inverter output
(For secondary side) (SW52-2)
Y
N
N
N
13: Switch motor drive source between
commercial power and inverter output
(For primary side) (SW52-1)
Y
N
N
N
15 (1015): Select AX terminal function
(For MC on primary side) (AX)
Y
Y
Y
Y
22 (1022): Inverter output limiting with delay (IOL2)
Y
Y
Y
Y
25 (1025): Cooling fan in operation (FAN)
Y
Y
Y
Y
26 (1026): Auto-resetting (TRY)
Y
Y
Y
Y
27 (1027): Universal DO (U-DO)
Y
Y
Y
Y
28 (1028): Heat sink overheat early warning (OH)
Y
Y
Y
Y
29 (1029): Synchronization completed (SY)
N
N
Y
N
30 (1030): Lifetime alarm (LIFE)
Y
Y
Y
Y
31 (1031): Frequency (speed) detected 2 (FDT2)
Y
Y
Y
Y
33 (1033): Reference loss detected (REF OFF)
Y
Y
Y
Y
35 (1035): Inverter output on (RUN2)
Y
Y
Y
Y
36 (1036): Overload prevention control (OLP)
Y
Y
Y
N
37 (1037): Current detected (ID)
Y
Y
Y
Y
38 (1038): Current detected 2 (ID2)
Y
Y
Y
Y
39 (1039): Current detected 3 (ID3)
Y
Y
Y
Y
41 (1041): Low current detected (IDL)
Y
Y
Y
Y
42 (1042): PID alarm (PID-ALM)
Y
Y
Y
N
43 (1043): Under PID control (PID-CTL)
Y
Y
Y
N
44 (1044): Motor stopped due to slow
flowrate under PID control (PID-STP)
Y
Y
Y
N
45 (1045): Low output torque detected (U-TL)
Y
Y
Y
Y
46 (1046): Torque detected 1 (TD1)
Y
Y
Y
Y
47 (1047): Torque detected 2 (TD2)
Y
Y
Y
Y
48 (1048): Motor 1 selected (SWM1)
Y
Y
Y
Y
49 (1049): Motor 2 selected (SWM2)
Y
Y
Y
Y
52 (1052): Running forward (FRUN)
Y
Y
Y
Y
53 (1053): Running reverse (RRUN)
Y
Y
Y
Y
54 (1054): In remote operation (RMT)
Y
Y
Y
Y
56 (1056): Motor overheat detected by thermistor (THM)
Y
Y
Y
Y
57 (1057): Brake signal (BRKS)
Y
Y
Y
N
58 (1058): Frequency (speed) detected 3 (FDT3)
Y
Y
Y
Y
59 (1059): Terminal [C1] wire break (C1OFF)
Y
Y
Y
Y
*1 6.00 s for inverters of 40 HP or below; 20.00 s for those of 50 HP or above
Item values in parentheses indicated value for negative logic.
Y: Applicable / N: Not Applicable.