E codes: Extension Terminal Functions
Code
Name
Data setting range
Change when
running
Data copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
Selecting function code data assigns the corresponding
function to terminals [X1] to [X7] as listed below.
4-71
E01
Terminal [X1] Function
0 (1000): Select multi-frequency (0 to 1 steps) (SS1)
N
Y
0
Y
Y
Y
N
E02
Terminal [X2] Function
1 (1001): Select multi-frequency (0 to 3 steps) (SS2)
N
Y
1
Y
Y
Y
N
E03
Terminal [X3] Function
2 (1002): Select multi-frequency (0 to 7 steps) (SS4)
N
Y
2
Y
Y
Y
N
E04
Terminal [X4] Function
3 (1003): Select multi-frequency (0 to 15 steps) (SS8)
N
Y
3
Y
Y
Y
N
E05
Terminal [X5] Function
4 (1004): Select ACC/DEC time (2 steps) (RT1)
N
Y
4
Y
Y
Y
N
E06
Terminal [X6] Function
5 (1005): Select ACC/DEC time (4 steps) (RT2)
N
Y
5
Y
Y
Y
N
E07
Terminal [X7] Function
6 (1006): Enable 3-wire operation (HLD)
N
Y
8
Y
Y
Y
Y
7 (1007): Coast to a stop (BX)
Y
Y
Y
Y
8 (1008): Reset alarm (RST)
Y
Y
Y
Y
9 (1009): Enable external alarm trip (THR)
(9 = Active OFF, 1009 = Active ON)
Y
Y
Y
Y
10 (1010): Ready for jogging (JOG)
Y
Y
Y
N
11 (1011): Select frequency command 2/1 (Hz2/Hz1)
Y
Y
Y
N
12 (1012): Select motor 2 (M2)
Y
Y
Y
Y
13: Enable DC braking (DCBRK)
Y
Y
Y
N
14 (1014): Select torque limiter level 2/1 (TL2/TL1)
Y
Y
Y
Y
15: Switch to commercial power (50 Hz) (SW50)
Y
N
N
N
16: Switch to commercial power (60 Hz) (SW60)
Y
N
N
N
17 (1017): UP (Increase output frequency) (UP)
Y
Y
Y
N
18 (1018): DOWN (Decrease output frequency) (DOWN)
Y
Y
Y
N
19 (1019): Enable data change with keypad (WE-KP)
Y
Y
Y
Y
20 (1020): Cancel PID control (Hz/PID)
Y
Y
Y
N
21 (1021): Switch normal/inverse operation (IVS)
Y
Y
Y
N
22 (1022): Interlock (IL)
Y
Y
Y
Y
23 (1023): Cancel torque control (Hz/TRQ)
N
N
N
Y
24 (1024):Enable communications link via
RS-485 or fieldbus (option) (LE)
Y
Y
Y
Y
25 (1025): Universal DI (U-DI)
Y
Y
Y
Y
26 (1026): Enable auto search for idling motor
speed at starting (STM)
Y
Y
N
Y
30 (1030): Force to stop (STOP)
(30 = Active OFF, 1030 = Active ON)
Y
Y
Y
Y
32 (1032): Pre-excitation (EXITE)
N
Y
Y
N
33 (1033): Reset PID integral and differential
components (PID-RST)
Y
Y
Y
N
34 (1034): Hold PID integral component (PID-HLD)
Y
Y
Y
N
35 (1035): Select local (keypad) operation (LOC)
Y
Y
Y
Y
39: Protect motor from dew condensation (DWP)
Y
Y
Y
Y
40: Enable integrated sequence to switch
to commercial power (50 Hz) (ISW50)
Y
N
N
N
41: Enable integrated sequence to switch
to commercial power (60 Hz) (ISW60)
Y
N
N
N
47 (1047): Servo-lock command (LOCK)
N
N
Y
N
48: Pulse train input (available only on
terminal [X7] (E07)) (PIN)
Y
Y
Y
Y
49 (1049): Pulse train sign (available on terminals
except [X7] (E01 to E06)) (SIGN)
59 (1059): Enable battery operation (BATRY)
Y
Y
Y
Y
Y
Y
Y
Y
70 (1070): Cancel constant peripheral speed
control (Hz/LSC)
Y
Y
Y
N
71 (1071): Hold the constant peripheral speed
control frequency in the memory (LSC-HLD)
Y
Y
Y
N
72 (1072): Count the run time of commercial
power-driven motor 1 (CRUN-M1)
Y
N
N
Y
73 (1073): Count the run time of commercial
power-driven motor 2 (CRUN-M2)
Y
N
N
Y
76 (1076): Select droop control (DROOP)
Y
Y
Y
N
77 (1077): Cancel PG alarm (PG-CCL)
N
N
Y
Y
80 (1080): Cancel customizable logic (CLC)
Y
Y
Y
Y
81 (1081): Clear all customizable logic timers (CLTC)
Y
Y
Y
Y
100: No function assigned (NONE)
Y
Y
Y
Y
Setting the value in parentheses ( ) shown above assigns a
negative logic input to a terminal.
The shaded function codes are applicable to the quick setup.
Y: Applicable / N: Not Applicable.