Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-3
F codes: Fundamental Functions
Code
Name
Data setting range
Change when
running
Data
copying
Default
setting
Drive control
Refer to
Page
V/f
Vector
Control
w/
PG
Torque
control
w/o
PG
F00
Data Protection
0: Disable both data protection and digital
reference protection
1: Enable data protection and disable digital
reference protection
2: Disable data protection and enable digital
reference protection
3: Enable both data protection and digital
reference protection
Y
Y
0
Y
Y
Y
Y
4-26
F01
Frequency Command 1
0: / keys on keypad
1: Voltage input to terminal [12] (-10 to +10
VDC)
2: Current input to terminal [C1] (4 to 20 mA
DC)
3: Sum of voltage and current inputs to
terminals [12] and [C1]
5: Voltage input to terminal [V2] (-10 to +10
VDC)
7: Terminal command UP/DOWN control
8: / keys on keypad
(balanceless-bumpless switching
available)
11: Digital input interface card (option)
12: Pulse train input
N
Y
0
Y
Y
Y
N
4-26
F02
Operation Method
0: Keypad
1: Terminal command FWD or REV
2: Keypad (Forward direction)
3: Keypad (Reverse direction)
N
Y
0
Y
Y
Y
Y
4-34
F03
Maximum Frequency 1
25.0 to 500.0 Hz
N
Y
60.0
Y
Y
Y
Y
F04
Base Frequency 1
25.0 to 500.0 Hz
N
Y
60.0
Y
Y
Y
Y
F05
Rated Voltage at Base Frequency 1
0: Output a voltage in proportion to
input voltage
80 to 240 V: Output an AVR-controlled
voltage
(for 230 V series)
160 to 500 V: Output an AVR-controlled
voltage
(for 460 V series)
N
Y2
230
460
Y
Y
Y
Y
F06
Maximum Output Voltage 1
80 to 240 V: Output an AVR-controlled
voltage
(for 230 V series)
160 to 500 V: Output an AVR-controlled
voltage
(for 460 V series)
N
Y2
230
460
Y
N
N
Y
F07
Acceleration Time 1
0.00 to 6000 s
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start.
Y
Y
*1
Y
Y
Y
N
4-37
F08
Deceleration Time 1
Y
Y
*1
Y
Y
Y
N
F09
Torque Boost 1
0.0% to 20.0% (percentage with respect to
"Rated Voltage at Base Frequency 1")
Y
Y
0.0
Y
N
N
N
4-40
4-56
F10
Electronic Thermal Overload Protection for
Motor 1
(Select motor characteristics)
1: For a general-purpose motor with
shaft-driven cooling fan
2: For an inverter-driven motor, non-ventilated
motor, or motor with separately powered
cooling fan
Y
Y
1
Y
Y
Y
Y
4-41
F11
(Overload detection level)
0.00: Disable
1% to 135% of the rated current (allowable
continuous drive current) of the motor
Y
Y1
Y2
*2
Y
Y
Y
Y
F12
(Thermal time constant)
0.5 to 75.0 min
Y
Y
*3
Y
Y
Y
Y
F14
Restart Mode after Momentary Power
Failure (Mode selection)
0: Trip immediately
1: Trip after a recovery from power failure
2: Trip after decelerate-to-stop
3: Continue to run, for heavy inertia or general
loads
4: Restart at the frequency at which the power
failure occurred, for general loads
5: Restart at the starting frequency
Y
Y
0
Y
Y
Y
N
4-43
F15
Frequency Limiter (High)
0.0 to 500.0 Hz
Y
Y
70.0
Y
Y
Y
N
4-49
F16
Frequency Limiter (Low)
0.0 to 500.0 Hz
Y
Y
0.0
Y
Y
Y
N
4-49
F18
Bias (Frequency command 1)
-100.00% to 100.00%
Y*
Y
0.00
Y
Y
Y
N
4-50
4-26
F20
DC Braking 1 (Braking starting frequency)
0.0 to 60.0 Hz
Y
Y
0.0
Y
Y
Y
N
4-50
F21
(Braking level)
0% to 80% (LD/MD mode) *4, 0% to 100%
(HD mode)
Y
Y
0
Y
Y
Y
N
F22
(Braking time)
0.00 (Disable); 0.01 to 30.00 s
Y
Y
0.00
Y
Y
Y
N
F23
Starting Frequency 1
0.0 to 60.0 Hz
Y
Y
0.5
Y
Y
Y
N
4-51
F24
(Holding time)
0.00 to 10.00 s
Y
Y
0.00
Y
Y
Y
N
F25
Stop Frequency
0.0 to 60.0 Hz
Y
Y
0.2
Y
Y
Y
N
The shaded function codes are applicable to the quick setup.
Y: Applicable / N: Not Applicable.