Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

3-4
3.3 Running Mode
3.3.1 Running or stopping the motor
By factory default, pressing the key starts running the motor in the forward direction and pressing the key
decelerates the motor to a stop. The
key is disabled. Running or stopping the motor with the keypad is enabled only
in Running and Programming modes.
To run the motor in reverse direction or run the motor in reversible mode, change the setting of function code F02.
For details of function code F02, refer to Chapter 4 "FUNCTION CODES."
Figure 3.2 Rotational Direction of Motor
Note) The rotational direction of an IEC-compliant motor is opposite to the one shown above.
Displaying the running status on the LCD monitor
(1) When function code E45 (LCD monitor item selection) is set at "0"
The LCD monitor displays the running status, the rotational direction, and the operation guide.
(The upper indicators show the unit of values displayed on the LED monitor as detailed in Section 3.3.2. The lower
ones show the running status and run command source.)
Figure 3.3 Display of Running Status
The running status and the rotational direction are displayed as shown in Table 3.3.
Table 3.3 Running Status and Rotational Direction
Status/Direction
Display
Meaning
Running status
RUN
STOP
A run command is given or the inverter is running the motor.
A run command is not given and the inverter is stopped.
Rotational direction
FWD
REV
Blank
Running in the forward rotation
Running in the reverse rotation
Stopped
Rotational direction
Running status
Operation guide