Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

9-4
9.3 Setpoint Scaling / Transducer Feedback Scaling (E40, E41)
Use parameter E40 and E41 to scale the EQ7 set-point to the transducer connected. Parameter E40 has to be
programmed to the maximum range of the transducer and E41 to the minimum range of the transducer.
To set parameter E40, E41
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to E40, E41 with UP/DOWN keys and press FUNC/DATA key to select.
Example 1: Example 2:
Transducer range: 0 – 150 PSI Transducer range: 0 – 80 PSI
E40 = 150.00 E40 = 80.00
E41 = 0.00 (default) E41 = 0.00 (default)
Use the and key to set the PID setpoint value
(E.g. 80.00 PSI)
Refer to the chapter 6 of the Instruction Manual for the preferred command (Run/Stop) method selection.