Instruction manual

Table Of Contents
9-3
Feedback Signal 0 10V (E61 = 5)
G
Connect shield to
ground terminal
3-Wire, 0 10V Transducer
+
Output
Analog Input, T12
Control Terminals /
User Terminals
Transducer Power:
Brown or Red: +
+10Vdc Power, T13
Transducer Output:
Black or White: 0 10V
Transducer Common:
Blue or Black: Common
Common/0V, T11
-
Program Feedback Signal Selection (E61, E62, E63)
Use the extended terminal functions to select the analog terminal to use for the feedback transducer. To do this,
determine the transducer specifications and then select the proper input terminal and electrical specifications from the
table.
Feedback Signal
Parameter Settings
Terminal 12 (0 10V)
E61 = 5
Terminal C1 (4 20mA)
E62 = 5
Terminal V2 (-10 10V)
E63 = 5
To set parameter E61, E62 and E63:
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to E61, E62 or E63 with UP/DOWN keys and press FUNC/DATA key to select.
E61
Terminal 12 Extended Function
E62
Terminal C1 Extended Function
E63
Terminal V2 Extended Function