Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

8-1
Chapter 8 Motor and Application Specific Settings
It is essential that before running the motor, the motor nameplate data matches the motor data in the EQ7 drive.
8.1 Set Motor Name Plate Data (P02, P03, F11)
The nominal motor rated capacity is set at the factory. Please verify that the motor name plate data matches the
motor rated capacity shown in parameter P02. The setting should only be changed when driving a motor with a
different capacity.
Range: 0.01 to 1000 HP
To set parameter P02:
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to P02 with UP/DOWN keys and press FUNC/DATA key to select.
Note: For kW rating motor set P99 to 4.
Default values vary based on the EQ7 drive model.
The motor rated current is set at the factory based on the EQ7 drive model. Enter the motor rated current from the
motor nameplate if it does not match the value shown in parameter P3.
This function sets the rated current value of motor 1.
Setting range: 0.00 to 2,000A
To set parameter P03:
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to P03 with UP/DOWN keys and press FUNC/DATA key to select.
This function sets the operation current level for the electronic thermal O/L. Verify that the motor FLA on the motor
nameplate matches the overload level shown in parameter F11
Setting range: 1 to 135% of the rated current of the inverter.
To set parameter F11:
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to F11 with UP/DOWN keys and press FUNC/DATA key to select.
P03
Motor 1 (Rated Current)
P02
Motor 1 (Capacity)
F11
Overload Detection Level