Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

7-1
Chapter 7 Operation Method Configuration (Run / Stop)
The EQ7 Drive offers users several choices to run and stop the drive from different sources. The most commonly
used methods are described in the next sections.
This function sets the operation method (Run/Stop) source.
Setting Range: 0 – 3
To set parameter F02:
- Press PRG key, next select QUICK SET or DATA SET with UP/DOWN and keys and press the
FUNC/DATA key.
- In the parameter list move cursor to F02 with UP/DOWN keys and press FUNC/DATA key to select.
Data for
F02
Run Command
Description
0
Keypad
Enables the , , and keys to run the motor in the
forward and reverse directions, and stop the motor.
1
Terminal command FWD or
REV
Enables input terminal commands FWD and REV to run
the motor in the forward and reverse directions, and stop
the motor.
2
Keypad
(Forward rotation)
Enables the and keys to run the motor in the forward
direction and stop it. Running the motor in the reverse
direction is not possible.
3
Keypad
(Reverse rotation)
Enables the and
keys to run the motor in the reverse
direction and stop it. Running the motor in the forward
direction is not possible.
7.1 Run/Stop from Keypad (Default Setting, F02 = 0)
Run from digital operator (Keypad) is the default setting.
Use the key to run the drive in forward direction and the
key to run the EQ7 drive in reverse direction. (Note: to
disable reverse direction set parameter H08 to 1)
Press key to stop the EQ7 drive. (Note: Stop method can be set with parameter H07, default is ramp to stop).
F02
Operation Method