Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

5-1
Chapter 5 Check Motor Rotation and Direction
This test is to be performed solely from the EQ7 drive keypad. Apply power to the EQ7 drive after all the electrical
connections have been made and protective covers have been re-attached. At this point, DO NOT RUN THE
MOTOR, the keypad should display as shown below in Fig. 5.1 and the speed reference 0.00 should be blinking.
Important: Motor rotation and direction only applies to standard AC motors with a base frequency of 60Hz.
Fig 5.1: Keypad (Stopped) Fig 5.2: Keypad (Running)
Next use the and keys to set a speed reference of 10.00 Hz, then press the key, see Fig 5.2.
The motor should now be operating at low speed running in forward (clockwise) direction.
Next press key to stop the motor.
If the motor rotation is incorrect, power down the EQ7 drive.
After the power has been turned OFF, wait at least ten minutes until the charge indicator extinguishes
completely before touching any wiring, circuit boards or components.
Using Safety precaution, and referring to Fig.2.23, exchange any two of the three output leads to the motor (U/T1,
V/T2 and W/T3). After the wiring change, repeat this step and recheck motor direction.