Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-104
E78, E79
E80, E81
Torque Detection 1 (Level and Timer)
Torque Detection 2/Low Torque Detection (Level and Timer)
E78 specifies the operation level and E79 specifies the timer, for the output signal TD1. E80 specifies the
operation level and E81 specifies the timer, for the output signal TD2 or U-TL.
Output signal
Assigned data
Operation level
Timer
Range: 0 to 300%
Range: 0.01 to 600.00 s
TD1
46
E78
E79
TD2
47
E80
E81
U-TL
45
E80
E81
Torque detected 1 -- TD1, Torque detected 2 -- TD2
The output signal TD1 or TD2 comes ON when the torque value calculated by the inverter or torque command
exceeds the level specified by E78 or E80 (Torque detection (Level)) for the period specified by E79 or E81
(Torque detection (Timer)), respectively. The signal turns OFF when the calculated torque drops below "the level
specified by E78 or E80 minus 5% of the motor rated torque." The minimum ON-duration is 100 ms.
Low output torque detected--U-TL
This output signal comes ON when the torque value calculated by the inverter or torque command drops below
the level specified by E80 (Low torque detection (Level)) for the period specified by E81 (Low torque detection
(Timer)). The signal turns OFF when the calculated torque exceeds the "level specified by E80 plus 5% of the
motor rated torque." The minimum ON-duration is 100 ms.
In the inverter’s low frequency operation, as a substantial error in torque calculation occurs, no low torque can be
detected within the operation range at less than 20% of the base frequency (F04). (In this case, the result of
recognition before entering this operation range is retained.)
The U-TL signal goes off when the inverter is stopped.
Since the motor parameters are used in the calculation of torque, it is recommended that auto-tuning be applied
by function code P04 to achieve higher accuracy.
E98, E99
Terminal [FWD] Function
Terminal [REV] Function (Refer to E01 to E07.)