Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-94
The operation timings of each signal are shown below.
E31, E32
Frequency Detection (Level and Hysteresis width) E36, E54 (Frequency Detection 2 and 3 (Level))
When the output frequency (estimated/detected speed) exceeds the frequency detection level specified by E31,
the "Frequency (speed) detected signal" comes ON; when it drops below the "Frequency detection level minus
Hysteresis width specified by E32," it goes OFF.
The following three settings are available.
Output signal
Data assigned
to output
terminal
Operation level
Hysteresis width
Range: 0.0 to 500.0
Hz
Range: 0.0 to 500.0
Hz
Frequency (speed)
detected signal FDT
2
E31
E32
Frequency (speed)
detected signal 2
FDT2
31
E36
Frequency (speed)
detected signal 3
FDT3
58
E54