Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-86
k ×speed Rated×
voltageRated×2
]5[-ltageBattery vo
operation battery during ramp)-(pre speed Reference
V
Figure C: Fan Power Supply Switching Connector
About battery operation (when BATRY is ON)
(1) The undervoltage protective function (lu ) is deactivated.
(2) The inverter can run the motor even under an undervoltage condition.
(3) The RDY ("Inverter ready to run") output signal is forcedly turned OFF.
(4) The bypass circuit of the charging resistor comes to be closed (73X ON) after a delay of time T1 from when the
BATRY is turned ON. Further, after a delay of time T2 (a maximum of 0.1 second), the battery operation starts. For
the specifications of T1, see the table below.
Battery Operation Timing Diagram
T1 from BATRY ON to 73X ON
Power condition
30 kW / 50 HP
or below
37 kW / 60 HP
or above
After the control power supply goes OFF, the
battery power and control power are turned ON.
100 ms
500 ms
The control power remains ON or after a
momentary power failure happens.
205 ms
(5) The S-curve acceleration/deceleration is disabled.
(6) The battery operation speed can be calculated by the following formula.
.
Where,
Battery voltage: 24 VDC or higher for 200 V class series / 230 V class series for USA
48 VDC or higher for 400 V class series / 460 V class series for USA.
Rated speed : F04
Rated voltage : F05 (Motor rated voltage (V))
Safety coefficient (Less than 1, about 0.8
When using R1 and T1 (BATRY operation)
Setting
CN R (Red)
Usage
CN W (White)
CN W (White)
When not using R1 or T1
(Factory default)
CN R (Red)
Main power
MC1
BATRY
MC2
73X
Battery power supply
DC link bus voltage Edc
Run command
Detected speed
Undervoltage level
Reference Frequency
T1
T2
Battery operation-
enabled zone
ON
ON
ON
ON
ON
ON
ON
ON
S-curve acce./dece. disabled
0
LU
ON
RDY
ON