Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-85
73X
MC2
R,S,T
N(-)
Battery
R0,T0
Control circuit
UPS
etc.
MC1
M
Edc
Converter
Power
Supply
+
Inverter
BATRY
Enable battery operation -- BATRY (Function code data = 59)
Turning this terminal command ON cancels the undervoltage protection so that the inverter runs the motor with
battery power under an undervoltage condition.
When BATRY is assigned to any digital input terminal, the inverter trips after recovery from power failure just as
F14 = 1 regardless of F14 setting. When BATRY is ON, the main power down detection is disabled regardless of
H72 setting.
Prerequisites for battery operation
(1) The terminal command BATRY (data = 59) must be assigned to any digital input terminal.
(2) A DC link bus voltage must be supplied from the battery to the main circuit (L1/R-L3/T or L2/S-L3/T) as shown
in Figures A and B given below.
(3) A regulated voltage (sine-wave or DC voltage) must be supplied to the auxiliary power supply (R0-T0).
(4) For 200 V class series / 230V class series 37 kW / 60 HP and above and 400 V class series / 460V 75 kW /
125 HP and above, a regulated voltage (sine-wave) must be supplied to the auxiliary fan power supply (R1-T1) as
shown in Figure B. The fan power supply connector must be configured for battery operation as shown in Figure C.
(5) The BATRY-assigned terminal (data = 59) must be turned ON at the same moment as closing of MC2.
Figure A: Connection Diagram
200 V Class: 30 kW (230V 50HP) and below
400 V Class: 55 kW, (460V 100HP) and Below
Figure B: Connection Diagram
200 V Class: 37 kW (230V 60HP) and above
400 V Class: 75 kW, (460V 125HP) and above
73X
MC2
R,S,T
N(-)
Battery
R0,T0
Control circuit
UPS
etc.
MC1
M
Edc
Converter
Power
Supply
+
Inverter
BATRY
R1,T1
Fan power supply