Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-84
3) Sequence with an emergency switching function --Part 2 (Automatic switching by the alarm output issued by
the inverter)
Servo-lock command -- LOCK (Function code data = 47)
Turning this terminal command ON enables a servo-lock command; turning it OFF disables a servo-lock
command. Refer to J97 through J99.
Pulse train input -- PIN (Function code data = 48)
Pulse train sign -- SIGN (Function code data = 49)
Assigning the command PIN to digital input terminal [X7] enables the frequency command by the pulse train input.
Assigning the command SIGN to one of the digital input terminals except [X7] enables the pulse train sign input to
specify the polarity of frequency command. Refer to F01.