Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-77
Example of Operation Time Scheme
Alternatively, set the integrated sequence by which some of the actions above are automatically
performed by the inverter itself. For details, refer to the description of ISW50 and ISW60.
UP Increase output frequency) and DOWN (Decrease output frequency) commands -- UP and DOWN
(Function code data = 17 and 18)
• Frequency setting
Turning the terminal command UP or DOWN ON causes the output frequency to increase or decrease,
respectively, within the range from 0 Hz to the maximum frequency. Refer to F01 (data = 7).
• PID command
Turning the terminal command UP or DOWN ON causes the PID command value to increase or decrease,
respectively, within the range from 0 to 100%. Refer to J02 (data = 3).
Enable data change with keypad PID control -- WE-KP (Function code data = 19)
Turning the terminal command WE-KP OFF protects function code data from accidentally getting changed by
pressing the keys on the keypad. Only when this terminal command is ON, you can change function code data
from the keypad. Refer to F00.