4-64
Torque limiter (Operating conditions) (H73)
H73 specifies whether the torque limiter is enabled or disabled during acceleration/deceleration and running at
constant speed.
Data for H73
During accelerating/decelerating
During running at constant speed
0
Enable
Enable
1
Disable
Enable
2
Enable
Disable
The torque limiter and current limiter are very similar in function. If both are activated concurrently, they
may conflict with each other and cause hunting (undesirable oscillation of the system). Avoid concurrent
activation of these limiters.