Instruction manual
Table Of Contents
- Preface
- Safety Precautions
- Table of Contents
- Warnings, Cautions and Conformity
- Chapter 1 Drive Model Identification
- Chapter 2 Mounting and Wiring the Inverter
- Chapter 3 Operation using the Keypad
- Chapter 4 Function Codes / Parameters
- Chapter 5 Check Motor Rotation and Direction
- Chapter 6 Speed Reference Command Configuration
- Chapter 7 Operation Method Configuration (Run / Stop)
- Chapter 8 Motor and Application Specific Settings
- Chapter 9 Using PID Control for Constant Flow / Pressure Applications
- Chapter 10 Troubleshooting
- 10.1 Protective Functions
- 10.2 Before Proceeding with Troubleshooting
- 10.3 If Neither an Alarm Code Nor "Light Alarm" Indication Appears on the LED Monitor
- 10.4 If an Alarm Code Appears on the LED
- 10.5 If the “Light Alarm” Indication Appears on the LED Monitor
- 10.6 If an Abnormal Pattern Appears on the LED Monitor except Alarm Codes and "Light Alarm" Indication
- 10.7 If the Inverter is Running on Single-Phase Power
- Chapter 11 Specifications

4-60
Torque limiter levels specified via communications link (S10, S11)
The torque limiter levels can be changed via the communications link. Function codes S10 and S11 exclusively
reserved for the communications link respond to function codes F40 and F41.
Switching torque limiters
The torque limiters can be switched by the function code setting and the terminal command TL2/TL1 ("Select
torque limiter level 2/1") assigned to any of the digital input terminals.
To assign the TL2/TL1 as the terminal function, set any of E01 through E07 to "14." If no TL2/TL1 is assigned,
torque limiter levels 1-1 and 1-2 (F40 and F41) take effect by default.
Torque limiter (Operating conditions) (H73)
H73 specifies whether the torque limiter is enabled or disabled during acceleration/deceleration and running at
constant speed.
Data for H73
During accelerating/decelerating
During running at constant speed
0
Enable
Enable
1
Disable
Enable
2
Enable
Disable
Torque limiter (Frequency increment limit for braking) (H76)
Data setting range: 0.0 to 500.0 (Hz)
H76 specifies the increment limit of the frequency in limiting torque for braking. The factory default is 5.0 Hz. If the
increasing frequency during braking reaches the limit value, the torque limiters no longer function, resulting in an
overvoltage trip. Such a problem may be avoided by increasing the setting value of H76.
The torque limiter and current limiter are very similar in function. If both are activated concurrently, they
may conflict with each other and cause hunting (undesirable oscillation of the system). Avoid concurrent
activation of these limiters.