Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
Power supply voltage
Nominal applied
motor
HP
Inverter type
CT//VT mode
Class J fuse size (A)
Circuit breaker trip size (A)
Required
torque lb-in
(Nm)
Wire size
AWG (mm
2
)
Main terminal
Aux. control power supply
Aux. Fan power supply
Main terminal
Aux. control power supply
Aux. fan power supply
L1/R, L2/S, L3/T
U, V, W
Three-
phase
Single-
phase
60C (140F)
Cu wire
75C (167F)
Cu wire
Remarks
60C (140F)
Cu wire
75C (167F)
Cu wire
Remarks
460 V
350
-
EQ7-4450-C
CT
800
600
424.7
(48)
10.6
(1.2)
10.6
(1.2)
-
300×2
(152×2)
-
*2
*3
-
350×2
(177×2)
-
*2
*3
14
(2.1)
*1
*2
14
(2.1)
*1
*2
450
125
VT
1000
400×2
(203×2)
400×2
(203×2)
400
EQ7-4500-C
CT
250×2
(127×2)
*2
*4
300×2
(152×2)
*2
*4
450
-
800
300×2
(152×2)
350×2
(177×2)
-
150
EQ7-4600-C
CT
500
EQ7-4500-C
VT
1200
400×2
(203×2)
400×2
(203×2)
-
EQ7-4600-C
CT
-
150
EQ7-4700-C
CT
600
200
EQ7-4600-C
VT
1200
500×2
(253×2)
500×2
(253×2)
-
EQ7-4700-C
CT
-
200
EQ7-4800-C
CT
700
EQ7-4700-C
VT
1400
600×2
(304×2)
600×2
(304×2)
-
EQ7-4800-C
CT
800
250
VT
1600
350×3
(177×3)
400×3
(203×3)
EQ7-4900-C
CT
900
300
VT
2000
1400
500×3
(253×3)
600×3
(304×3)
EQ7-41000-C
CT
1000
400
VT
2200
1600
600×3
(304×3)
500×4
(253×4)
Note: Control circuit terminals Tightening torque: 6.1 lb-in (0.7 Nm), Recommended wire size: AWG 19 or 18 (0.65 to 0.82 mm
2
)
*1 No terminal end treatment is required for connection.
*2 Use 75C (167F) Cu (Copper) wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.
*4 It is showing the wire size for UL Open Type.
See additional material INR-SI47-1365
-JE for UL Enclosed Type (Pack with TYPE1 kit).